BiDi: transmission in both directions on a single fibre. How it works and when it pays off

A classic optical link uses two fibres: on one, data runs in one direction, on the other, in the opposite direction. A BiDi transceiver serves both directions on a single fibre, separating them by wavelength. The effect is simple to calculate: the same number of fibres serves twice as many links.


It is a solution that pays off most where fibre is a scarce or expensive resource: when leasing from an operator, in congested telecom ducts, and everywhere that adding a cable means a construction project. Below we explain how it works, when the numbers favour BiDi, and when it is better to reach for another solution.

One fibre carries two wavelengths in opposite directions

The example of the 1270 and 1330 nm pair, typical for 10G links
Transceiver, variant U
transmits 1270 nm
receives 1330 nm
location A
1270 nm
1330 nm
one fibre, simplex LC connector
Transceiver, variant D
transmits 1330 nm
receives 1270 nm
location B

One side's transmit wavelength must be the other side's receive wavelength, which is why BiDi transceivers work only in pairs. Two transceivers of the same variant will never establish a link.

How it works


Inside the BiDi transceiver housing, next to the laser and the photodiode, sits a WDM filter called a diplexer. Its job is a single one, that is to separate the outgoing light from the incoming light on the basis of wavelength. The laser transmits on one wavelength, and the filter directs that signal into the fibre. At the same time a signal returns from the fibre on a different wavelength, and the same filter deflects it toward the photodiode. Both signals run in the same fibre in opposite directions and do not interfere with one another, because they occupy different spectral windows.

Why transceivers work only in pairs


Here lies the whole difference from an ordinary duplex transceiver. If the transceiver on side A transmits at 1310 nm, then the transceiver on side B must receive at 1310 nm and transmit on the other wavelength of the pair. The transceiver on side A in turn must receive exactly that other wavelength. For this reason BiDi transceivers are sold as complementary variants, usually marked with the letters U and D or A and B. Two transceivers of the same variant will never establish a link, because both will transmit on the same wavelength and both will listen on the same one.

The connector


Since there is a single fibre, the connector is single too. A BiDi transceiver has a simplex LC socket, not a duplex one. In some manufacturers' tables the entry LC duplex appears, which can be a source of confusion when ordering patch cords. For a BiDi link you need a single-fibre patch cord.

Typical wavelength pairs


Pairs from the 1270 and 1330 nm range lie close together in the O-band, where the chromatic dispersion of G.652 fibre is near zero. This simplifies the design and lowers the price, but the attenuation in this band is higher than at 1550 nm, which shortens the reach. Widely spaced pairs, such as 1310 and 1550 nm, give a greater reach at the cost of a more expensive filter.

ApplicationWavelength pairTypical reach
1G, access and campus networks1310 / 1550 nm or 1310 / 1490 nm3–40 km
10G, metro and data centres1270 / 1330 nm10–60 km
10G, long routes1490 / 1550 nm80–100 km
25G1270 / 1330 nm10–40 km
100G1271 / 1331 nm10–40 km, depending on the variant

The numbers: BiDi, a fibre pair, or CWDM


Three solutions to the same problem, that is sending data between two points. They differ in how many fibres they use and how much they cost. Let us assume common premises: four 10G links between two locations, fibre leased from an operator, a rate of 120 PLN per kilometre of fibre per year.

Common premises: 4 x 10G links, leased fibre, rate of 120 PLN per kilometre of fibre per year. The amounts are the annual lease cost.
Distance 5 kmwithin the city
Fibre pair8 fibres, cheapest hardware4,800 PLN
BiDi4 fibres, transceivers dearer by a few dozen percent2,400 PLN
CWDM2 fibres, plus the cost of multiplexers1,200 PLN

The saving on the lease does not cover the difference in hardware price. If you have free fibres, an ordinary pair wins. BiDi makes sense when fibres are scarce.

Distance 20 kmBiDi wins
Fibre pair8 fibres19,200 PLN
BiDi4 fibres, the surcharge pays back in the first year9,600 PLN
CWDM2 fibres, multiplexers pay back more slowly4,800 PLN

A saving of 9,600 PLN per year against a one-off surcharge on the order of a few thousand zloty. Simple hardware, no passive devices, immediate payback.

Distance 60 kmnumbers lean toward CWDM
Fibre pair8 fibres57,600 PLN
BiDi4 fibres, long-reach 1490/1550 nm transceivers28,800 PLN
CWDM2 fibres, multiplexers pay back quickly14,400 PLN

Above a few dozen kilometres the numbers tip toward CWDM, especially when the number of links is set to grow. BiDi remains reasonable with a fixed, small number of connections.

BiDi is strongest in the range from a dozen to a few dozen kilometres with a small and stable number of links. Below that range the saving does not cover the hardware surcharge. Above it, or with a growing number of services, it is better to invest in wavelength multiplexing.

BiDi across the individual speeds

1Gmost mature
1310/1550 nm1310/1490 nm3–40 km

Present in access networks for years, with broad manufacturer support, a low price, and predictable behaviour. Typically connections between buildings, links to the customer, and campus networks.

10Gmost common choice
1270/1330 nm1490/1550 nmup to a few dozen km

Today the most frequently chosen variant for metro network modernisation. For an operator with a working single-fibre infrastructure at 1G, it is the natural expansion path without touching the passive layer.

25Ggrowing
1270/1330 nmup to 40 kmSFP28

A segment growing alongside deployments of fifth-generation access networks. SFP28 housing.

100GQSFP28
1271/1331 nm10 to a few dozen km

For an operator that has a single fibre on the route and wants to raise the throughput from 10G to 100G without building a new cable.

BiDi in PON networks


It is worth noting something that is rarely said outright: all of PON is by definition single-fibre bidirectional transmission. GPON transmits downstream at 1490 nm and upstream at 1310 nm, XGS-PON at 1577 and 1270 nm respectively. This is exactly the same principle as in BiDi, applied in a point-to-multipoint architecture instead of point-to-point. That is why a passive splitter in a PON network works on a single fibre, not a pair. If you understand how a BiDi transceiver works, you also understand the physical basis of a PON network.

Limitations worth knowing about

The filter costs decibels

The diplexer introduces insertion loss, usually on the order of 1 to 1.5 dB at each end of the link. On a route calculated with minimal margin, switching from a two-fibre link to BiDi can absorb the entire reserve.

Back-reflections matter more

In BiDi the transmitted and received signals share one fibre, so reflections from connectors and backscatter return to the receiver of the same transceiver. Connector cleanliness stops being a matter of hygiene and becomes a condition for operation.

Diagnostics are harder

A reflectometer measurement on a fibre carrying traffic in both directions at once requires taking the link down or using a wavelength outside the working pair. Locating a fault takes more time than on a two-fibre path.

A failure of one fibre takes down both directions

Obvious, but it tends to be overlooked in risk analysis. In a two-fibre link, breaking one fibre gives, in some architectures, a chance of degradation instead of a total loss of connectivity. In BiDi there is no such scenario.

Not everything called BiDi is single-fibre

Some 40G and 100G products on multimode fibre, described as BiDi, use two fibres. The same name, a different principle. When ordering, check the connector type: simplex LC means one fibre, duplex LC means two.

Five mistakes that recur most often

✕
Two transceivers of the same variant

A classic when ordering a round number of units. Ten BiDi transceivers are not ten links, but five pairs. When ordering, give the number of links and make sure you get complementary variants in equal numbers.

✕
A duplex patch cord with a simplex transceiver

The transceiver has one socket, the cable has two plugs. The installer plugs in one, and the dangling second one collects dust and sooner or later ends up in someone's hands. For BiDi links, order single-fibre patch cords.

✕
No variant marking on the transceiver

After a year nobody remembers which side has which variant, and at replacement time the guessing begins. Mark transceivers at installation, and record the variant in the as-built documentation together with the port number.

✕
Mixed-up bands during expansion

Transceivers at 1270 and 1330 nm and at 1310 and 1550 nm are two different worlds. When adding a link, check which pair the already-installed transceivers work on. Mixing pairs on the same route ends in no link or an unstable one.

✕
A power budget calculated for a two-fibre link

When migrating from a fibre pair to BiDi, the budget has to be recalculated from scratch, accounting for the filter loss on both sides. A module with a nominal reach of 20 km will not always replace a pair of modules of the same reach on the same route.

A selection table

SituationSolutionWhy
You have free fibres, distance up to a few kilometresfibre paircheapest hardware, simplest diagnostics
Fibres are scarce, a few links, up to 40 kmBiDidoubles capacity without work in the passive layer
You lease fibre, 10–60 km, a fixed number of linksBiDithe saving on the lease pays back the hardware in the first year
A growing number of services on one routeCWDMscales to 18 channels without adding fibre
Distance above 60 km, many servicesCWDM DWDMmultiplexing and the ability to amplify the signal
A need for dozens of channels or hundreds of kilometresDWDMthe only technology in this class
A point-to-multipoint access networkPONsingle-fibre transmission with division among subscribers

Three questions settle the choice. First, how many free fibres do I have on this route and what does it cost to add another? If fibres are plentiful and free, BiDi has no economic justification. Second, how many links will I have on this route in three years? A fixed number argues for BiDi, a growing one for wavelength multiplexing. Third, what margin do I have in the optical power budget? If below 3 dB, switching to BiDi requires modules of greater reach or a recalculation of the whole route.

Rozpocznij z nami nowy projekt!
Dziękujemy! Otrzymaliśmy Twoje zgłoszenie!
Ups! Wystąpił błąd podczas wysyłania formularza.

DML or EML?

Two types of DML and EML lasers are used in 100G optical modules. Which one to choose? Which one will be best for you?
Czytaj więcej

How will the new year change the telco and data center industry?

Savings, climate-neutral infrastructure and O-band. Salumanus experts share their knowledge and experience forecasting trends for 2023.
Czytaj więcej

SRD 5 — new optical module programmer

Salumanus announces the launch of Smart Recode Device 5 GBC Photonics (SRD 5). It is an optical module programmer that allows you to save thousands of dollars on the management of optical networks.
Czytaj więcej